Непрерывное измерение уровня
Сравнительная таблица непрерывных направленных РАДАРНЫХ уровнемеров
Levelflex M FMP40 |
Levelflex M FMP41C |
|
Characteristic / Application |
· Coaxial probe: · Rod probe: · Rope probe: |
Coated probe for corrosive liquids · Rod probe · Rope probe: |
Supply / Communication |
2-wire ( HART / PA / FF ) |
2-Draht ( HART / PA / FF) |
Accuracy |
· Coaxial probe: +/- 3 mm · Rod probe: +/- 3 mm · Rope probe: +/- 0.03% |
· Rod probe: +/- 3 mm · Rope probe: +/- 0.03% |
Ambient temperature |
-40 °C ... 80 °C |
-40 °C ... 80 °C |
Process temperature |
-40 °C ... 150 °C |
-40 °C ... 200 °C |
Process pressure absolute / max. overpressure limit |
Vacuum ... 40 bar |
Vakuum ... 40 bar |
Wetted parts |
· Coaxial probe: 316L, Alloy C22 |
PTFE |
Process connection |
G + NPT 3/4" and 1/2", DN40 ... DN150 |
DN40 ... DN150 |
Hygienic |
Triclamp 1 1/2", 2", 3" |
|
Sensor length |
Rod: 4 m |
Rod: 4m |
Max. measurement distance |
· Coaxial probe : 4 m Min. DK > 1.4 |
· Rod probe : 4 m Min. DK > 1.6 |
Output |
4 ... 20 mA HART |
4 ... 20 mA HART |
Certificates / Approvals |
ATEX |
SIL |
Application limits |
· Coaxial probe: · Rod probe: Viscosity > 5000 cst · Lateral load > 30 Nm · Rope probe: Viscosity > 5000 cst · Moved liquid |
· Rod probe: Viscosity > 5000 cst · Lateral load > 30 Nm · Rope probe: Viscosity > 5000 cst · Moved liquid |
Техническая документация
- Levelflex М FМР 40
Непрерывные УЛЬТРАЗВУКОВЫЕ уровнемеры
Техническая документация
Непрерывные ЕМКОСТНЫЕ уровнемеры
Техническая документация
Сравнительная таблица непрерывных дифференциально-разностных уровнемеров
Deltabar S PMD70 |
Deltabar S PMD75 |
Deltabar S FMD76 |
Deltabar S FMD77 |
Deltabar S FMD78 |
Deltabar S PMD230 |
Deltabar S PMD235 |
Deltabar S FMD230 |
Deltabar S FMD630 |
Deltabar S FMD633 |
|
Characteristic / Application |
Digital transmitter with ceramic measuring diapragms Modular transmitter Long term stability Enhanced safety via self diagnostic functions Secondary process barrier |
Digital transmitter with metallic measuring diaphragms Modular transmitter Long term stability High static pressure/Overload resistance Enhanced safety via self diagnostic functions Secondary process barrier | Digital transmitter with ceramic measuring diaphragms Modular transmitter Long term stability Enhanced safety via self diagnostic functions High resistance to abrasion Secondary process barrier |
Digital transmitter with metallic measuring diaphragms one side with diaphragm seal Modular transmitter Long term stability Enhanced safety via self diagnostic functions Secondary process barrier |
Digital transmitter with metallic measuring diaphragms diaphragm seals and capillaries Modular transmitter Long term stability Enhanced safety via self diagnostic functions Secondary process barrier |
Digital differential pressure transmitter, capacitive sensor with ceramic diaphragm Safety by function monitoring and membrane detection, modular transmitter design |
Digital differential pressure transmitter with metal measuring diaphragm Safety by function monitoring, modular transmitter design |
Digital differential pressure transmitter for hydrostatic level measurement, capacitive sensor with flush mounted ceramic measuring diaphragm Safety by function monitoring and membrane detection, modular transmitter design |
Digital differential pressure transmitter for hydrostatic level measurement with diaphragm seal on process Safety by function monitoring, modular transmitter design |
Digital differential pressure transmitter with capillary diaphragm seals Safety by function monitoring, modular transmitter design |
Supply / Communication |
4...20mA HART: PROFIBUS PA / Foundation Fieldbus: |
4...20mA HART: PROFIBUS PA / Foundation Fieldbus: |
4...20mA HART: PROFIBUS PA / Foundation Fieldbus: |
4...20mA HART: PROFIBUS PA / Foundation Fieldbus: |
4...20mA HART: PROFIBUS PA / Foundation Fieldbus: |
4...20mA / HART: PROFIBUS PA / Foundation Fieldbus: |
4...20mA / HART: PROFIBUS PA / Foundation Fieldbus: |
4...20mA / HART: PROFIBUS PA / Foundation Fieldbus: |
4...20mA / HART: PROFIBUS PA / Foundation Fieldbus: |
4...20mA / HART: PROFIBUS PA / Foundation Fieldbus: |
Accuracy |
0,075% "PLATINUM" 0,05% |
0,075% "PLATINUM" 0,05% |
0,075% "PLATINUM" 0,05% |
0,075% + influence of diapragm seal | 0,075% + influence of diapragm seal | 0,1% | 0,1% "PLATINUM" 0,05% |
0,1% | 0,1% | 0,1% |
Long term stability |
0,05% of URL/year | 0,05% of URL/year | 0,05% of URL/year | 0,05% of URL/year | 0,05% of URL/year | 0,1% of URL/year 0,25% of URL/5 years |
0,1% of URL/year 0,25% of URL/5 years |
0,1% of URL/year 0,25% of URL/5 years |
0,1% of URL/year 0,25% of URL/5 years |
0,1% of URL/year 0,25% of URL/5 years |
Ambient temperature |
-40...85°C | -40...85°C | -40...85°C | -40...85°C | -40...85°C | -40...85°C | -40...85°C | -40...85°C | -40...85°C | -40...85°C |
Process temperature |
-40...85°C | -40...120°C | -40...85°C | -40...350°C | -40...350°C | -40...85°C | -40...120°C | -40...85°C | -40...350°C | -40...350°C |
Process pressure absolute / max. overpressure limit |
150bar | 420bar | 100bar | 160bar | 160bar | 100bar | 420bar | 100bar | 160bar | 160bar |
Pressure measuring range |
25mbar...3bar | 10mbar...40bar | 100mbar...3bar | 100mbar...16bar | 100mbar...40bar | 25mbar...3bar | 10mbar...40bar | 100mbar...3bar | 100mbar...16bar | 100mbar...16bar |
Wetted parts |
Ceramic Alloy C 316L Monel Tantal |
Alloy C 316L Monel Tantal |
Ceramic Alloy C 316L Monel Tantal |
Alloy C 316L Monel Tantal |
Alloy C 316L Monel Tantal |
Alloy C 316L Monel Tantal |
Alloy C 316L Monel Tantal |
Alloy C 316L Monel Tantal |
Alloy C 316L Monel Tantal |
Alloy C 316L Monel Tantal |
Process connection |
1/4-18NPT RC1/4" |
1/4-18NPT RC1/4" |
1/4-18NPT RC1/4" Flanges (DIN, ANSI, JIS) |
Low pressure side: 1/4-18NPT RC1/4" High pressure side: Flanges (DIN, ANSI, JIS) |
Diaphragm seal (Pancake, threads) Flanges (DIN, ANSI) Tri-Clamp Hygienic connections |
1/4-18NPT RC1/4" |
1/4-18NPT RC1/4" |
1/4-18NPT RC1/4" Flanges (DIN, ANSI, JIS) |
Low pressure side: 1/4-18NPT RC1/4" High pressure side: Flanges (DIN, ANSI, JIS) |
Diaphragm seal (Pancake, threads) Flanges (DIN, ANSI) Tri-Clamp Hygienic connections |
Max. measurement distance |
30m H2O | 400m H2O | 30m H2O | 160m H2O | 400m H2O | 30m H2O | 400m H2O | 30m H2O | 160m H2O | 160m H2O |
Output |
4...20mA HART PROFIBUS PA Foundation Fieldbus |
4...20mA HART PROFIBUS PA Foundation Fieldbus |
4...20mA HART PROFIBUS PA Foundation Fieldbus |
4...20mA HART PROFIBUS PA Foundation Fieldbus |
4...20mA HART PROFIBUS PA Foundation Fieldbus |
4 ... 20mA HART Profibus PA Foundation Fieldbus |
4 ... 20mA HART PROFIBUS PA Foundation Fieldbus |
4 ... 20mA HART PROFIBUS PA Foundation Fieldbus |
4 ... 20mA HART PROFIBUS PA Foundation Fieldbus |
4 ... 20mA HART PROFIBUS PA Foundation Fieldbus |
Certificates / Approvals |
ATEX FM CSA SIL GL marine WHG/overspill protection 3.1.B material inspection certificate |
ATEX FM CSA SIL NACE GL marine WHG/overspill protection 3.1.B material inspection certificate |
ATEX FM CSA SIL GL marine WHG/overspill protection 3.1.B material inspection certificate |
ATEX FM CSA SIL NACE GL marine WHG/overspill protection 3.1.B material inspection certificate |
ATEX FM CSA SIL NACE GL marine WHG/overspill protection 3.1.B material inspection certificate |
ATEX FM CSA SIL WHG/overspill protection 3.1.B material inspection certificate |
ATEX FM CSA TIIS SIL NACE WHG/overspill protection 3.1.B material inspection certificate |
ATEX FM CSA SIL WHG/overspill protection 3.1.B material inspection certificate |
ATEX FM CSA TIIS SIL NACE WHG/overspill protection 3.1.B material inspection certificate |
ATEX FM CSA TIIS SIL NACE WHG/overspill protection 3.1.B material inspection certificate |
Options |
HistoROM/M-Dat 4-line digital display SS- or Aluminiumhousing |
HistoROM/M-Dat 4-line digital display SS- or Aluminiumhousing |
HistoROM/M-Dat 4-line digital display SS- or Aluminiumhousing |
HistoROM/M-Dat 4-line digital display SS- or Aluminiumhousing |
HistoROM/M-Dat 4-line digital display SS- or Aluminiumhousing |
digital display SS- or Aluminumhousing |
digital display SS- or Aluminumhousing |
digital display SS- or Aluminumhousing |
digital display SS- or Aluminumhousing |
digital display SS- or Aluminumhousing |
Application limits |
Changing density | Changing density | Changing density | Changing density | Changing density | Changing density | Changing density | Changing density | Changing density | Changing density |
Successor |
PMD70 | PMD75 | FMD76 | FMD77 | FMD78 |
Техническая документация
Сравнительная таблица непрерывных ГИДРОСТАТИЧЕСКИХ уровнемеров
Waterpilot FMX165 |
Waterpilot FMX167 |
Deltapilot S DB50 |
Deltapilot S DB50L |
Deltapilot S DB51 |
Deltapilot S DB52 |
Deltapilot S DB53 |
Deltapilot S DB50A |
Deltapilot S DB50S |
Deltapilot S DB51A |
Deltapilot S DB52A |
Deltapilot S DB53A |
Cerabar M PMC41 |
Cerabar M PMC45 |
Cerabar M PMP41 |
Cerabar M PMP45 |
Cerabar M PMP46 |
Cerabar M PMP48 |
Cerabar S PMC71 |
Cerabar S PMP71 |
Cerabar S PMP72 |
Cerabar S PMP75 |
Cerabar S PMC731 |
Cerabar S PMP731 |
Cerabar S PMC631 |
Cerabar S PMP635 |
|
Characteristic / Application |
Pressure transmitter for hydrostatic level rope probe, capacitive flush mounted sensor with ceramic measuring diaphragm Sensor pipe diameter 42mm |
Pressure transmitter for hydrostatic level rope probe with ceramic measuring diaphragm Sensor pipe diameter 22mm |
Pressure transmitter, gauge for hydrostatic level measurement, flush mounted CONTITE-sensor with metallic measuring diaphragm Alloy C4 hermetically welded + safe humidity protection Compact version |
Pressure transmitter, gauge for hydrostatic level measurement, flush mounted CONTITE-sensor with metallic measuring diaphragm Alloy C4 hermetically welded + safe humidity protection Compact version Hygienic design |
Pressure transmitter, gauge for hydrostatic level measurement, flush mounted CONTITE-sensor with metallic measuring diaphragm Alloy C4 hermetically welded + safe humidity protection Rod version |
Pressure transmitter, gauge for hydrostatic level measurement, flush mounted CONTITE-sensor with metallic measuring diaphragm Alloy C4 hermetically welded + safe humidity protection Rope version |
Pressure transmitter, gauge for hydrostatic level measurement, flush mounted CONTITE-sensor with metallic measuring diaphragm Alloy C4 hermetically welded + safe humidity protection Rope version with mounting clamp |
Pressure transmitter, gauge for hydrostatic level measurement, flush mounted CONTITE-sensor with metallic measuring diaphragm Alloy C4 hermetically welded + safe humidity protection Compact version |
Pressure transmitter, gauge for hydrostatic level measurement, flush mounted CONTITE-sensor with metallic measuring diaphragm Alloy C4 hermetically welded + safe humidity protection Compact version Hygienic design |
Pressure transmitter, gauge for hydrostatic level measurement, flush mounted CONTITE-sensor with metallic measuring diaphragm Alloy C4 hermetically welded + safe humidity protection Rod version |
Pressure transmitter, gauge for hydrostatic level measurement, flush mounted CONTITE-sensor with metallic measuring diaphragm Alloy C4 hermetically welded + safe humidity protection Rope version |
Pressure transmitter, gauge for hydrostatic level measurement, flush mounted CONTITE-sensor with metallic measuring diaphragm Alloy C4 hermetically welded + safe humidity protection Rope version with mounting clamp |
Smart and reliable pressure transmitter, capacitive sensor with ceramic measuring diaphragm | Smart and reliable pressure transmitter, capacitive sensor with ceramic flush mounted diaphragm for hygienic applications | Smart and reliable pressure transmitter, piezoresistive polysilicon sensor, welded metal diaphragm | Smart and reliable pressure transmitter, piezoresistive polysilicon sensor, welded metal diaphragm for hygienic applications | The smart and reliable pressure transmitter with diaphragm seals for hygienic applications | Smart and reliable pressure transmitter with diaphragm seal | Digital transmitter with capacitive sensor and ceramic membrane Modular transmitter Long term stability Enhanced safety via self diagnostic functions Secondary process barrier |
Digital transmitter with piezoresistive sensor and welded metallic membrane Modular transmitter Long term stability Enhanced safety via self diagnostic functions Secondary process barrier |
Digital transmitter Hightemperature version without diaphragm seal Modular transmitter Long term stability Enhanced safety via self diagnostic functions Secondary process barrier |
Digital transmitter with piezoresistive sensor and diaphragm seal Modular transmitter Long term stability Minimum oil volume process connection Enhanced safety via self diagnostic functions Secondary process barrier |
Digital pressure transmitter, capacitive wetted sensor with ceramic diaphragm Safety by funcion monitoring, modular transmitter design |
Digital pressure transmitter, piezoresistive polysilicon sensor with welded metal measuring diaphragm Safety by function monitoring, modular transmitter design |
Digital pressure transmitter with diaphragm seal for hygienic applications Safety by function monitoring, modular transmitter design |
Digital pressure transmitter with diaphragm seal Safety by funcion monitoring, modular transmitter design |
Supply / Communication |
12..30V DC | 10...30V DC Ex ia: 10...30V DC |
3-wire analogue: 2-wire PFM-Signal: 4...20mA HART: PROFIBUS PA: Foundation Fieldbus: |
3-wire analogue: 2-wire PFM-Signal: 4...20mA HART: PROFIBUS PA: Foundation Fieldbus: |
3-wire analogue: 2-wire PFM-Signal: 4...20mA HART: PROFIBUS PA: Foundation Fieldbus: |
3-wire analogue: 2-wire PFM-Signal: 4...20mA HART: PROFIBUS PA: Foundation Fieldbus: |
3-wire analogue: 2-wire PFM-Signal: 4...20mA HART: PROFIBUS PA: Foundation Fieldbus: |
3-wire analogue: 2-wire PFM-Signal: 4...20mA HART: PROFIBUS PA: Foundation Fieldbus: |
3-wire analogue: 2-wire PFM-Signal: 4...20mA HART: PROFIBUS PA: Foundation Fieldbus: 9...32V DC |
3-wire analogue: 2-wire PFM-Signal: 4...20mA HART: PROFIBUS PA: Foundation Fieldbus: |
3-wire analogue: 2-wire PFM-Signal: 4...20mA HART: PROFIBUS PA: Foundation Fieldbus: |
3-wire analogue: 2-wire PFM-Signal: 4...20mA HART: PROFIBUS PA: Foundation Fieldbus: |
Analogue: HART: PROFIBUS PA: |
Analogue: HART: PROFIBUS PA: |
Analogue: HART: PROFIBUS PA: |
Analogue: HART: PROFIBUS PA: |
Analogue/HART: PROFIBUS PA: |
Analogue/HART: PROFIBUS PA: |
4...20mA HART: PROFIBUS PA / Foundation Fieldbus: |
4...20mA HART: PROFIBUS PA / Foundation Fieldbus: |
4...20mA HART: PROFIBUS PA / Foundation Fieldbus: |
4...20mA HART: PROFIBUS PA / Foundation Fieldbus: |
4...20mA HART: PROFIBUS PA / Foundation Fieldbus: |
4...20mA HART: PROFIBUS PA / Foundation Fielbus: |
4...20mA HART: PROFIBUS PA / Foundation Fieldbus: |
4...20mA HART: PROFIBUS PA / Foundation Fieldbus: |
Accuracy |
0,2% | 0,2% | 0,2% optional 0,1% |
0,2% optional 0,1% |
0,2% optional 0,1% |
0,2% optional 0,1% |
0,2% optional 0,1% |
0,2% optional 0,1% |
0,2% optional 0,1% |
0,2% optional 0,1% |
0,2% optional 0,1% |
0,2% optional 0,1% |
0,2% optional 0,1% |
0,2% optional 0,1% |
0,2% optional 0,1% |
0,2% optional 0,1% |
0,2% | 0,2% | 0,075% "PLATINUM" 0,05% |
0,075% "PLATINUM" 0,05% |
0,075% "PLATINUM" 0,05% |
0,075% + influence of diapragm seal | 0,1% | 0,1% | 0.2% | 0,2% |
Long term stability |
0,1% of URL/year | 0,1% of URL/year | 0,1% of URL/6 months | 0,1% of URL/6 months | 0,1% of URL/6 months | 0,1% of URL/6 months | 0,1% of URL/6 months | 0,1% of URL/6 months | 0,1% of URL/6 months | 0,1% of URL/6 months | 0,1% of URL/6 months | 0,1% of URL/6 months | 0,1% of URL/year 0,25% of URL/3 years |
0,1% of URL/year 0,25% of URL/3 years |
0,1% of URL/year 0,25% of URL/3 years |
0,1% of URL/year 0,25% of URL/3 years |
0,1% of URL/year 0,25% of URL/3 years |
0,1% of URL/year 0,25% of URL/3 years |
0,05% of URL/year | 0,05% of URL/year | 0,05% of URL/year | 0,05% of URL/year | 0,1% of URL/year 0,25% of URL/5 years |
0,1% of URL/year 0,25% of URL/5 years |
0,1% of URL/year | 0,1% of URL/year |
Ambient temperature |
0...70°C | -10...70°C | -40...85°C | -40...85°C | -40...85°C | -40...85°C | -40...85°C | -40...85°C | -40...85°C | -40...85°C | -40...85°C | -40...85°C | -40..85°C | -40...85°C | -40...85°C | -40...85°C | -40...85°C | -40...85°C | -40...85°C | -40...85°C | -10...85°C | -40...85°C | -40...85°C | -40...85°C | -40...85°C | -40...85°C |
Process temperature |
0...70°C | -10..70°C | -10...100°C | -10...100°C | -10...80°C | -10...80°C | -10...80°C | -10...100°C | -10...100°C | -10...80°C | -10...80°C | -10...80°C | -40...100°C | -40...125°C (150°C/1h) | -40...100°C | -40...125°C (150°C/1h) | -40..350°C | -40..350°C | -40...150°C | -40...125°C | -10...280°C | -40...350°C | -40...100°C | -40...100°C | -40...350°C | -40...350°C |
Process pressure absolute / max. overpressure limit |
40bar | 40bar | 25bar | 25bar | 25bar | 25bar | 25bar | 362,5psi | 362,5psi | 362,5psi | 362,5psi | 362,5psi | 60bar | 60bar | 600bar | 600bar | 160bar | 600bar | 60bar | 1050bar | 160bar | 1050bar | 60bar | 600bar | 60bar | 600bar |
Pressure measuring range |
100mbar...20bar | 100mbar...20bar | 100mbar...10bar | 100mbar...10bar | 100mbar...10bar | 100mbar...10bar | 100mbar...10bar | 1,5psi...150psi | 1,5psi...150psi | 1,5psi...150psi | 1,5psi...150psi | 1,5psi...150psi | 100mbar...40bar | 100mbar...40bar | 1bar...400bar | 1bar...400bar | 1bar...40bar | 1bar...400bar | 100mbar...40bar | 100mbar...700bar | 100mbar...40bar | 100mbar...700bar | 100mbar...40bar | 1bar...400bar | 400mbar...40bar | 1bar...400bar |
Wetted parts |
Ceraphire ceramic Dichtung 316Ti |
Sealing 316L |
Alloy C 316L |
Alloy C 316L |
Alloy C 316L |
Alloy C 316L Cable (PE/FEP) |
Alloy C 316L Cable (PE/FEP) |
Alloy C 316L |
Alloy C 316L |
Alloy C 316L |
Alloy C 316L Cable (PE/FEP) |
Alloy C 316L Cable (PE/FEP) |
Ceraphire ceramic Sealing Alloy C 316L |
Ceraphire ceramic Sealing 316L |
316L | 316L | 316L | Alloy C 316L | Ceraphire ceramic Alloy C 316L Monel PVDF |
Alloy C 316L Monel |
316L | Alloy C 316L Monel Tantal PTFE-Foil |
Ceraphire ceramic Alloy C 316L PVDF |
Alloy C 316L Tantal PTFE-Foil |
Ceraphire ceramic Alloy C 316L Tantal PTFE-Foil |
Alloy C 316L Tantal PTFE-Foil |
Process connection |
Mounting clamp | Mounting clamp | Threads Flanges (DIN, ANSI, JIS) |
Universal process mounting adapter Tri-Clamp Hygienic connections |
Threads Flanges (DIN, ANSI, JIS) |
Threads Flanges (DIN, ANSI, JIS) |
Mounting clamp | Threads Flanges (ANSI) |
Universal process mounting adapter Tri-Clamp |
Threads Flanges (ANSI) |
Threads Flanges (ANSI) |
Mounting clamp | Threads | Threads Flanges (DIN, ANSI, JIS) Tri-Clamp Hygienic connections |
Threads | Threads Tri-Clamp Hygienic connections |
Tri-Clamp Hygienic connections |
Threads Flanges (DIN, ANSI, JIS) |
Threads (internal/flush mounted membrane) Flanges (DIN, ANSI, JIS) with flush mounted membrane |
Threads (interanal/flush mounted membrane) Flanges (DIN, ANSI, ...) with flush mounted mebrane |
Threads (flush mounted membrane) Flanges (DIN, ANSI) with flush mounted membrane |
Threads (flush mounted membrane) Flanges (DIN, ANSI, JIS) with flush mounted membrane Tri-Clamp Hygienic connections |
Threads Flanges (DIN, ANSI, JIS) Tri-Clamp hygienic connections |
Threads (internal/flush mounted membrane) | Tri-Clamp Hygienic connections |
Threads Flanges (DIN, ANSI) |
Max. measurement distance |
200m H2O | 200m H2O | 100m H2O | 100m H2O | 100m H2O | 100m H2O | 100m H2O | 100m H2O | 100m H2O | 100m H2O | 100m H2O | 100m H2O | 400m H2O | 400m H2O | 4000m H2O | 4000m H2O | 400m H2O | 4000m H2O | 400m H2O | 7000m H2O | 400m H2O | 7000m H2O | 400m H2O | 4000m H2O | 400m H2O | 4000m H2O |
Output |
4...20mA | 4..20mA 4..20mA 4-wire (with integrated T-sensor) |
3-wire analogue 2-wire PFM 4...20mA HART PROFIBUS PA Foundation Fieldbus |
3-wire analogue 2-wire PFM 4...20mA HART PROFIBUS PA Foundation Fieldbus |
3-wire analogue 2-wire PFM 4...20mA HART PROFIBUS PA Foundation Fieldbus |
3-wire analogue 2-wire PFM 4...20mA HART PROFIBUS PA Foundation Fieldbus |
3-wire analogue 2-wire PFM 4...20mA HART PROFIBUS PA Foundation Fieldbus |
3-wire analogue 2-wire PFM 4...20mA HART PROFIBUS PA Foundation Fieldbus |
3-wire analogue 2-wire PFM 4...20mA HART PROFIBUS PA Foundation Fieldbus |
3-wire analogue 2-wire PFM 4...20mA HART PROFIBUS PA Foundation Fieldbus |
3-wire analogue 2-wire PFM 4...20mA HART PROFIBUS PA Foundation Fieldbus |
3-wire analogue 2-wire PFM 4...20mA HART PROFIBUS PA Foundation Fieldbus |
4..20mA analogue 4..20mA HART PROFIBUS PA |
4...20mA analogue 4...20mA HART PROFIBUS PA |
4...20mA analogue 4...20mA HART PROFIBUS PA |
4...20mA analogue 4...20mA HART PROFIBUS PA |
4...20mA analogue 4...20mA HART PROFIBUS PA |
4...20mA analogue 4...20mA HART PROFIBUS PA |
4...20mA HART PROFIBUS PA Foundation Fieldbus |
4...20mA HART PROFIBUS PA Foundation Fieldbus |
4...20mA HART PROFIBUS PA Foundation Fieldbus |
4...20mA HART PROFIBUS PA Foundation Fieldbus |
4...20mA HART PROFIBUS PA Foundation Fieldbus |
4...20mA HART PROFIBUS PA Foundation Fieldbus |
4..20mA HART PROFIBUS PA Foundation Fieldbus |
4..20mA HART PROFIBUS PA Foundation Fieldbus |
Certificates / Approvals |
ATEX GL Marine |
ATEX FM CSA NSF |
ATEX CSA TIIS WHG/overspill protection GL Marine 3.1.B material inspection certificate |
ATEX CSA WHG/overspill protection GL Marine 3A EHDG 3.1.B material inspection certificate |
ATEX CSA TIIS WHG/overspill protection |
ATEX CSA TIIS WHG/overspill protection GL Marine |
ATEX CSA TIIS GL Marine |
FM CSA 3.1.B material inspection certificate |
FM CSA 3A EHEDG 3.1.B material inspection certificate |
FM CSA |
FM CSA |
FM CSA |
ATEX FM CSA SIL GL Marine 3.1.B material inspection certificate |
ATEX FM CSA SIL GL Marine 3A EHEDG 3.1.B material inspection certificate |
ATEX FM CSA SIL GL Marine 3.1.B material inspection certificate |
ATEX FM CSA SIL GL Marine 3A 3.1.B material inspection certificate |
ATEX FM CSA SIL GL Marine 3A 3.1.B material inspection certificate |
ATEX FM CSA SIL GL Marine 3.1.B material inspection certificate |
ATEX FM CSA SIL GL marine WHG/overspill protection 3.1.B material inspection certificate |
ATEX FM CSA SIL NACE GL marine WHG/overspill protection 3.1.B material inspection certificate |
ATEX FM CSA SIL NACE GL marine WHG/overspill protection 3.1.B material inspection certificate |
ATEX FM CSA SIL NACE GL marine WHG/overspill protection 3.1.B material inspection certificate |
ATEX FM CSA TIIS SIL NACE 3.1.B material inspection certificate |
ATEX FM CSA TIIS SIL NACE 3.1.B material inspection certificate |
ATEX FM CSA SIL 3.1.B material inspection certificate |
ATEX FM CSA TIIS SIL NACE 3.1.B material inspection certificate |
Options |
PE or FEP-cable changeable probe customer specific adjustment |
integrated temperature sensor PE or FEP-cable customer specific adjustment |
digital display SS-, Aluminium- or Polyesterhousing |
digital display SS-, Aluminium- or Polyesterhousing |
digital display SS-, Aluminium- or Polyesterhousing |
digital display SS-, Aluminium- or Polyesterhousing |
digital display SS-, Aluminium- or Polyesterhousing |
digital display SS-, Aluminium- or Polyesterhousing |
digital display SS-, Aluminium- or Polyesterhousing |
digital display SS-, Aluminium- or Polyesterhousing |
digital display SS-, Aluminium- or Polyesterhousing |
digital display SS-, Aluminium- or Polyesterhousing |
digital display SS- or Aluminumhousing |
digital display SS- or Aluminumhousing |
digital display SS- or Aluminumhousing |
digital display SS- or Aluminumhousing |
digital display SS- or Aluminumhousing |
digital display SS- or Aluminumhousing |
HistoROM/M-Dat 4-line digital display SS- or Aluminiumhousing |
HistoROM/M-Dat 4-line digital display SS- or Aluminiumhousing |
HistoROM/M-Dat 4-line digital display SS- or Aluminiumhousing |
HistoROM/M-Dat 4-line digital display SS- or Aluminiumhousing |
digital display SS- or Aluminumhousing |
digital display SS- or Aluminumhousing |
digital display SS- or Aluminumhousing |
digital display SS- or Aluminumhousing |
Specialities |
Easy cleanable SS-housing with Ra < 0,8 microns | Easy cleanable SS-housing with Ra < 0,8 micron | Easy cleanable SS-housing with Ra < 0,8 micron | |||||||||||||||||||||||
Application limits |
Changing density | Changing density | Changing density | Changing density | Changing density | Changing density | Changing density | Changing density | Changing density | Changing density | Changing density | Changing density | Changing density | Changing density | Changing density | Changing density | Changing density | Changing density | Changing density | Changing density | Changing density | Changing density | Changing density | Changing density | Changing density | Changing density |
Successor |
PMC71 | PMP71, PMP72 | PMC71, PMP75 | PMP75 |
Техническая документация
Сравнительная таблица непрерывных радиометрических уровнемеров
DETECTOR DG57 |
|
Characteristic / Application |
Scintillation detector |
Supply / Communication |
Transmitter |
Ambient temperature |
-20°C...50°C 40°C...120°C with cooling jacket |
Process temperature |
Any |
Process pressure absolute / max. overpressure limit |
Any |
Wetted parts |
Contactless |
Process connection |
Contactless |
Hygienic |
Contactless |
Sensor length |
400mm...2000mm >2000mm cascade mode |
Max. measurement distance |
Unlimited measuring range
|
Output |
PCM |
Certificates / Approvals |
ATEX TIIS |
Options |
Kontilot for large measuring ranges |
Specialities |
Interface measurement Calculation and sizing with Applicator CD-ROM |
Components |
Source: Cs137, Co60 Source container: QG020, QG100, QG2000 Transmitter: FMG671 (P) |
Техническая документация
Электромеханические уровнемеры / Уровнемеры с серводвигателями
Техническая документация